WHITE BROWN DA 918 Manual de usuario Pagina 93

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 127
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 92
5-24 | ni.com
Chapter 5 Counters
Counter Output Applications
The following sections list the various counter output applications available on the cDAQ
chassis:
Simple Pulse Generation
Pulse Train Generation
Frequency Generation
Frequency Division
Pulse Generation for ETS
Simple Pulse Generation
Refer to the following sections for more information about the cDAQ chassis simple pulse
generation options:
Single Pulse Generation
Single Pulse Generation with Start Trigger
Single Pulse Generation
The counter can output a single pulse. The pulse appears on the Counter n Internal Output signal
of the counter.
You can specify a delay from when the counter is armed to the beginning of the pulse. The delay
is measured in terms of a number of active edges of the Source input.
You can specify a pulse width. The pulse width is also measured in terms of a number of active
edges of the Source input. You also can specify the active edge of the Source input (rising or
falling).
Figure 5-26 shows a generation of a pulse with a pulse delay of four and a pulse width of three
(using the rising edge of Source).
Figure 5-26. Single Pulse Generation
SOURCE
OUT
Counter Armed
Vista de pagina 92
1 2 ... 88 89 90 91 92 93 94 95 96 97 98 ... 126 127

Comentarios a estos manuales

Sin comentarios